| Primary Purpose | Establishes rating and test conditions for electrically driven air conditioners, liquid chilling packages, heat pumps for space heating and cooling, and process chillers. | Defines safety and environmental requirements for refrigerating systems and heat pumps across their life cycle, including design, installation, operation, maintenance, repair, and disposal. | IEC 60335-1 provides general household and similar electrical-appliance safety requirements. IEC 60335-2-40 adds appliance-specific requirements for electrical heat pumps, air conditioners, and dehumidifiers. | Market-specific legislation may govern electrical safety, pressure equipment, refrigerants, energy efficiency, noise, electromagnetic compatibility, installation, and waste handling. | Ask for the exact standard editions used, the laboratory test report, the declaration of conformity, and the list of target countries. |
| High-Temperature Capability | Allows comparable performance reporting at defined test conditions. The standard does not itself guarantee that a product can continuously deliver a particular leaving-water temperature. | Requires safety controls and system design appropriate to operating pressures, refrigerant charge, temperature, ventilation, servicing, and foreseeable abnormal conditions. | Addresses construction, protection against electric shock, abnormal operation, temperature rise, wiring, clearances, and safeguards relevant to heat-pump appliances. | Some jurisdictions impose additional requirements for hot-water systems, pressure equipment, building services, or high-temperature applications. | Confirm the certified leaving-water temperature, outdoor operating range, maximum discharge temperature, capacity at design conditions, and whether auxiliary electric heating is required. |
| Performance Data | Performance is measured under specified conditions such as air or water temperatures, flow rate, entering and leaving temperatures, and electrical input. Results should identify the tested operating point. | Focuses primarily on safety and environmental requirements rather than providing a single global efficiency-rating method. | Safety compliance does not replace independent verification of heating capacity, coefficient of performance, seasonal efficiency, or sound power. | Energy-label or minimum-efficiency rules may use different regional methods. For example, the European Union uses separate ecodesign and energy-labelling requirements for relevant product categories. | Compare capacity and COP at the same water temperatures, outdoor temperatures, defrost conditions, pump power assumptions, and supply voltage. |
| Refrigerant Selection | Performance testing should identify the refrigerant and charge used because refrigerant choice affects pressure, capacity, temperature lift, and efficiency. | Requires risk-based consideration of refrigerant toxicity, flammability, charge, occupied-space installation, ventilation, detection, service procedures, and environmental impact. | Contains appliance safety provisions for refrigerants, including requirements relevant to flammable refrigerants when applicable. The applicable refrigerant safety classification should be identified. | Refrigerant controls vary by country and region. They may include restrictions on high global-warming-potential refrigerants, technician certification, recovery, recordkeeping, and leak checks. | Record the refrigerant designation, safety class, charge mass, GWP value used by the target jurisdiction, maximum allowable charge, and required service qualifications. |
| Pressure and Mechanical Safety | Provides test conditions for performance but is not a complete pressure-equipment design code. | Covers pressure-related hazards, protective devices, piping, installation, operation, maintenance, and repair considerations for refrigerating systems and heat pumps. | Covers appliance construction and electrical safety; it should be used together with applicable pressure and refrigerating-system requirements. | Pressure equipment rules may apply to the circuit, vessels, piping, safety accessories, and conformity-assessment route. Requirements differ by jurisdiction and pressure category. | Check design pressure, relief-device settings, pressure-test records, vessel and piping documentation, and the conformity route required in each destination market. |
| Electrical Compatibility | Test results should state electrical supply conditions and auxiliary energy assumptions so that reported performance can be compared correctly. | Includes safety considerations related to installation and operation of refrigerating systems, but it is not a complete electrical product standard. | Verify rated voltage, frequency, protective earthing, insulation, leakage current, overcurrent protection, control safety, and abnormal-operation performance. | National wiring rules, grid-connection requirements, EMC rules, radio requirements, and product safety schemes may apply in addition to IEC-based testing. | Confirm compatibility with local voltage and frequency, phase arrangement, maximum current, short-circuit rating, disconnect requirements, and harmonics or power-quality limits. |
| Installation Environment | Test conditions are controlled and may not represent every field environment, such as coastal air, dust, altitude, low ambient temperature, or unstable voltage. | Addresses installation, room volume, ventilation, access, refrigerant concentration, emergency procedures, servicing, and operating conditions. | Includes appliance construction and protection requirements that depend on installation conditions and foreseeable use. | Building, fire, electrical, seismic, acoustic, accessibility, and refrigerant-installation codes may impose additional requirements. | Specify ambient-temperature limits, altitude, corrosion category, snow and wind exposure, indoor room volume, ventilation, drainage, service clearance, and acoustic limits. |
| Controls and Protective Functions | Performance data should state control mode, setpoints, defrost strategy, and any capacity limitation used during testing. | Requires protection against foreseeable hazards such as excessive pressure, refrigerant release, inadequate ventilation, unsafe servicing, and abnormal operating conditions. | Evaluates safety-related controls, limiting devices, abnormal operation, component temperature, and protection against electric and thermal hazards. | Local rules may require emergency shutoff, refrigerant detection, ventilation interlocks, anti-legionella controls for domestic hot water, or specific fire-safety measures. | Check high- and low-pressure protection, flow protection, freeze protection, over-temperature cutout, leak response, restart behavior, alarms, and fail-safe operation. |
| Documentation and Traceability | Performance reports should identify the unit configuration, test conditions, measurement method, refrigerant, and relevant tolerances. | Requires appropriate information for installation, operation, maintenance, repair, safety, and environmental handling. | Requires safety-related markings, instructions, ratings, warnings, and technical information appropriate to the appliance. | Importers or authorities may require declarations, technical files, test reports, labels, translated manuals, registration, and installer or refrigerant-handling records. | Obtain manuals, wiring diagrams, refrigerant circuit drawings, spare-parts information, commissioning sheets, maintenance intervals, and warranty conditions. |
| Recommended Compliance Status | Performance reference | System safety reference | Appliance safety reference | Mandatory by destination | Verify for each country |