| 2-wire RTD connection | The instrument measures the PT100 element through two leads. | Lead resistance is included in the measured resistance and can create a temperature error. The effect increases with longer or thinner leads. | Short cable runs or applications where the resulting measurement error is acceptable. | Check cable length, conductor size, and the allowed measurement error. |
| 3-wire RTD connection | A third lead lets a compatible instrument compensate for lead resistance. | Compensation generally assumes the lead resistances are similar; mismatched leads can leave residual error. | Common industrial installations where a practical balance of wiring cost and measurement performance is needed. | Confirm that the input supports 3-wire RTDs and use leads with matching material, gauge, and length where practical. |
| 4-wire RTD connection | One pair supplies the measuring current and a separate pair senses the voltage at the element. | The separate sensing leads largely eliminate the effect of lead resistance on the measured resistance. | Long cable runs or measurements requiring better control of lead-related error. | Verify that the instrument supports 4-wire measurement and that the extra conductors are available. |
| Direct resistance input | An RTD-capable input module or instrument measures the PT100 resistance and converts it to temperature. | Depends on the selected 2-, 3-, or 4-wire connection and the input’s compensation method. | Systems that can accept a sensor directly and need the temperature conversion performed at the controller or measurement device. | Check PT100 compatibility, supported wiring, input range, excitation current, and configured sensor curve. |
| 4–20 mA transmitter | A transmitter measures the RTD and sends a current proportional to a configured temperature range. | The transmitter’s RTD input wiring determines lead compensation; the current output is generally suitable for transmitting a signal over longer cable runs. | Industrial control systems using current-loop inputs or installations where a conditioned signal is preferred. | Match the transmitter’s RTD input and wiring to the sensor, and configure the temperature range, loop supply, and receiver input. |
| 0–10 V transmitter output | A transmitter converts the measured temperature into a voltage across a configured range. | RTD lead compensation is handled at the transmitter input; the voltage signal can be more affected by electrical noise and voltage drop than a current-loop signal. | Control systems with compatible voltage inputs and relatively short or electrically quiet signal wiring. | Check the receiver’s input range, grounding arrangement, cable environment, and transmitter output range. |
| Digital transmitter or interface | A compatible device converts the RTD measurement and communicates temperature digitally over its supported protocol. | Lead compensation depends on the device’s RTD input wiring; the digital link has its own cable, distance, and network requirements. | Systems that need digital configuration, diagnostics, or integration with a supported communication network. | Confirm protocol compatibility, power and wiring requirements, network limits, and available diagnostics. |