| Applicable Design Standard | IEC 60076 series or IEEE C57 standards, according to the project location and utility requirements. | The applicable standard defines design, insulation, temperature-rise, testing, and performance requirements. | Request the exact standard edition, compliance statement, design drawings, and routine test reports. |
| Rated Power | Select the required kVA or MVA rating based on the calculated maximum demand, diversity, motor starting current, and future load growth. | An undersized transformer may overheat or suffer voltage drop, while excessive oversizing can increase purchase and no-load operating costs. | Confirm the continuous rating, overload capability, ambient conditions, and the calculation used for the selected capacity. |
| Primary and Secondary Voltage | Specify the exact system voltages, such as 11 kV / 0.4 kV or another project-defined combination, including voltage tolerances. | Correct voltage matching is essential for safe operation, equipment compatibility, and acceptable secondary voltage. | Verify rated voltage, highest voltage for equipment, insulation level, neutral arrangement, and connection to the site network. |
| Frequency and Phase | Normally 50 Hz or 60 Hz, with single-phase or three-phase construction as required by the electrical system. | Frequency and phase affect magnetic flux, losses, impedance, protection settings, and compatibility with connected loads. | Confirm rated frequency, phase configuration, phase sequence, and suitability for the local utility supply. |
| Vector Group and Neutral | Choose the required vector group, such as Dyn11, and specify whether the low-voltage neutral is brought out and grounded. | Vector group determines phase displacement and affects parallel operation, fault behavior, and grounding arrangements. | Confirm the vector group, neutral terminal size, grounding method, phase displacement, and parallel-operation requirements. |
| Percentage Impedance | A commonly specified distribution-transformer range is approximately 4% to 6%, subject to the fault-current and voltage-drop study. | Impedance influences short-circuit current, voltage regulation, load sharing, and protection coordination. | Request guaranteed impedance tolerance, positive and zero-sequence impedance where applicable, and short-circuit withstand data. |
| Energy Efficiency | Evaluate guaranteed no-load loss, load loss, total loss at the specified loading point, and compliance with applicable efficiency regulations. | Transformers remain energized for long periods, so no-load and load losses have a significant effect on lifetime operating cost. | Ask for guaranteed loss values, measurement tolerances, loss evaluation conditions, and the calculation of total cost of ownership. |
| Temperature Rise and Cooling | Specify the permitted top-oil and winding temperature rise according to the selected standard and site ambient conditions; common cooling designations include ONAN. | Temperature directly affects insulation aging, service life, overload capability, and reliability. | Confirm maximum ambient temperature, altitude correction, cooling mode, temperature-rise test results, and thermal monitoring provisions. |
| Insulating Liquid | Use a suitable mineral insulating oil or approved alternative fluid with appropriate dielectric strength, oxidation stability, and environmental properties. | The liquid provides insulation and transfers heat; its quality affects fire risk, maintenance, and long-term dielectric performance. | Confirm liquid type, applicable fluid standard, inhibited or uninhibited formulation, fluid test results, and environmental documentation. |
| Tank and Sealing System | Select a sealed-tank or conservator design with adequate mechanical strength, corrosion protection, and leak-resistant joints. | Moisture ingress and oil leakage reduce insulation performance and can shorten transformer service life. | Check pressure or vacuum testing, coating system, gasket materials, tank thickness, leak-test records, and corrosion category suitability. |
| Tap-Changer Arrangement | Use an off-circuit tap changer for de-energized voltage adjustment, or an on-load tap changer where voltage must be regulated while energized. | Tap selection helps compensate for supply-voltage variation and maintain the required secondary voltage. | Confirm tap range, typical options such as ±2 × 2.5% or ±5%, operating mechanism, position indication, and interlocking requirements. |
| Insulation and Lightning Protection | Define rated insulation levels, power-frequency withstand voltage, lightning impulse withstand voltage, and surge-arrester coordination. | Proper insulation coordination reduces the risk of failure caused by lightning, switching surges, and network disturbances. | Request insulation-level schedules, impulse-test records where applicable, bushing ratings, creepage distance, and surge-protection recommendations. |
| Accessories and Monitoring | Typical accessories may include oil-level indicator, pressure-relief device, thermometer, drain valve, lifting lugs, earthing terminals, and temperature alarm contacts. | Correct accessories support safe installation, condition monitoring, maintenance, and rapid fault response. | Confirm the accessory list, alarm and trip contacts, control voltage, wiring diagram, terminal-box rating, and spare-parts availability. |
| Routine and Type Testing | Routine tests commonly include winding resistance, ratio and phase displacement, impedance and load loss, no-load loss and current, dielectric tests, and leak checks. | Documented testing verifies that the manufactured unit conforms to the approved design and guaranteed performance. | Require signed test reports, calibration certificates, inspection and test plans, witness-test options, and independent inspection arrangements. |
| Manufacturer Reliability | Evaluate proven experience with comparable voltage and power ratings, documented quality systems, production capability, and after-sales support. | A technically suitable design can still create project risk if manufacturing controls, delivery capability, or service support are inadequate. | Review reference installations without relying only on marketing claims, quality certificates, warranty terms, lead time, service response, and spare-parts support. |
| Installation Environment | Specify indoor or outdoor use, altitude, ambient temperature, humidity, pollution level, seismic conditions, enclosure requirements, and available space. | Environmental conditions affect cooling, insulation performance, corrosion protection, dimensions, and installation safety. | Confirm all site data, derating requirements, cable-entry arrangement, foundation loads, sound limits, fire-safety requirements, and maintenance clearances. |
| Documentation and Acceptance | Require an approved datasheet, dimensional drawing, nameplate, wiring diagram, installation manual, operation manual, certificates, and final test dossier. | Complete documentation supports approval, installation, commissioning, maintenance, and future replacement planning. | Agree on the document-submittal schedule, approval procedure, factory acceptance test requirements, warranty coverage, and final acceptance criteria. |