| What RCCB means | RCCB stands for residual current circuit-breaker without integral overcurrent protection. It is a type of RCD (residual current device). | It detects residual current—an imbalance between the current flowing in the live conductors—and disconnects the circuit when its operating conditions are met. |
| Why an RCCB is used | It provides residual-current protection, which can reduce the risk of electric shock and help limit the risk of fire caused by certain earth-leakage faults. | An RCCB does not, by itself, provide protection against overloads or short circuits. It must be coordinated with a suitable overcurrent protective device. |
| 30 mA rating | 30 mA is the rated residual operating current, written as IΔn. It is the device’s specified sensitivity rating, not a guarantee that every fault will be disconnected in exactly the same time. | Choose and install the device in accordance with the applicable wiring rules, product requirements, circuit conditions and manufacturer instructions. |
| Socket-outlets and outdoor mobile equipment | IEC 60364-4-41, Clause 411.3.3 requires additional protection by an RCD in AC systems for specified socket-outlets rated up to 32 A that are likely to be used by ordinary persons and intended for general use, and for mobile equipment rated up to 32 A used outdoors. | The clause includes limited exceptions for certain socket-outlets, subject to the conditions in the applicable edition and national adoption. Check local regulations before applying an exception. |
| Lighting circuits in household premises | IEC 60364-4-41, Clause 411.3.4 requires additional protection by RCDs with a rated residual operating current not exceeding 30 mA for AC final circuits supplying luminaires in household premises. | This requirement applies where Clause 411.3.4 is adopted in the governing edition or national rules. Confirm the edition and any local amendments. |
| Additional protection is not the only protection | Clause 415.1 describes additional protection by RCDs with a rated residual operating current not exceeding 30 mA. | An RCD is an additional protective measure; it does not replace basic protection, protective earthing, automatic disconnection requirements or other measures required for the installation. |
| RCCB versus RCBO | An RCCB has no integral overcurrent protection. An RCBO combines residual-current protection with overcurrent protection. | Use an RCCB with suitable overcurrent protection, or use an appropriately rated RCBO where the installation design calls for both functions in one device. |